VENT HOOD TERMINAT
TERMINATION CLEARANCES FOR CANADIAN INSTALLATIONS
The SS1-R has been CSA Listed according to the requirements of “Mechanical Flue-Gas Exhausters” CSA Std B255-M81 and
the “Installation code for Oil burning Equipment” CSA Std B139-M91. (See Diagram. A1)
A venting system shall not terminate underneath a veranda, porch, or deck, or above a paved sidewalk or a paved driveway
that is located between two buildings, and that serves both buildings.
The exit terminals of mechanical draft systems shall not be less than 2.13m (7ft) above grade when located adjacent to a paved
sidewalk or driveway.
A venting system shall not direct flue gases towards brickwork, siding, or other construction, in such a manner that may cause
damage from heat or condensate from the flue gases.
A venting system shall not direct flue gases so as to jeopardize people, overheat combustible structures, or enter buildings.
A venting system shall not terminate within 1.8 m (6ft) of the following:
A window, door or mechanical air supply inlet of any building, including soffit openings
A gas service regulator vent outlet
A combustion air inlet
A property line
A direction facing combustible materials or openings of surrounding buildings
A venting system shall not terminate within 1m (3ft) of the following:
Above a gas meter/regulator assembly within 1m (3ft) horizontally of the vertical centreline of the regulator
A oil tank or an oil tankfill inlet
The inside corner of an L-shaped structure
A venting system shall not terminate within .3m (1ft) of the following:
Above grade level or any surface that may support snow, ice, or debris
It is not recommended for the SS1-R to be terminated on a wall that faces the direction of
the prevailing winds. Backdrafts by severe winds can cause oil odors to remain in the
structure and/or interrupt heating equipment operation.
6