Copyright © 2014, Tjernlund Products, Inc. All rights reserved P/N 8504208
OWNER INSTRUCTIONS, DO NOT DESTROY
Recognize this symbol as an indication of important Safety Information!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND
OPERATION OF THIS PRODUCT. READ THESE INSTRUCTIONS THOROUGHLY
BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW
THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUST-
MENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRI-
CAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, PERSONAL
INJURY OR PROPERTY DAMAGE.
!
WARNING
!
DO NOT DESTROY. PLEASE READ CAREFULLY AND
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
MODEL COP2
(Includes COP2 Control and Transducer)
INSTALLATION INSTRUCTIONS
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com
Seitenansicht 0
1 2 3 4 5 6 ... 10 11

Inhaltsverzeichnis

Seite 1 - INSTALLATION INSTRUCTIONS

Copyright © 2014, Tjernlund Products, Inc. All rights reserved P/N 8504208OWNER INSTRUCTIONS, DO NOT DESTROYRecognize this symbol as an indication of

Seite 2

9If voltage to and from the Transducer are in the ranges listed above, measure COP2 VFD output AC voltage at the Red andWHT/RED stripe terminals with

Seite 3 - FROM ROOFTOP FAN

10TJERNLUND LIMITED ONE YEAR WARRANTYTjernlund Products, Inc. warrants to the original purchaser of this product that the product will be free from de

Seite 4

1TABLE OF CONTENTSPage (s)Description and General Information...

Seite 5

2SIZING A COMMON VENT MANIFOLD SERVING MULTIPLE DRYERSThe most important step towards assuring that individual dryers vented into a common manifold ex

Seite 6 - DIAGRAM F

3PRESSURE SENSING TUBE LOCATIONMULTIPLE DRYERS JOINED IN A COMMON HORIZONTAL DUCTThe sensing tube should be installed in the vent cap of a tee or at t

Seite 7 - TJERNLUND

4PRESSURE SENSING TUBE INSTALLATION1. Follow sensing tube location recommendations on page 3. Use a sharp drill bit to reduce burr, drill a 1/4"

Seite 8 - IN = OFF (Away from You)

5IMPORTANTThe capacitor for the RT-Series fan should remain within the junction box of the flexible whip. Do not install within fan motor compartment.

Seite 9

6NL1COP2 SYSTEM WIRINGPOWER SUPPLY115 VACGROUNDWHTBLKREDWHT / REDCOOLING FANEXHAUSTERMOTORFIGUREGRYGRYVIOYELREDV+COM1-10P2P1C2C1 REDGRNWHTBLKL1NWHT511

Seite 10

7ADJUSTING THE EXHAUST PRESSURE SET POINT The pressure set point is adjusted by positioning dip switches 6 - 1 to match the desired setting listed on

Seite 11

8ADJUSTMENT OF BALANCING BAFFLE(S) FOR KITCHEN AND BATH FANSIMPORTANT: Balancing Baffles must not be used for dryer applications due to the potential