Copyright © 2002, Tjernlund Products, Inc. All rights reserved P/N 8504102
OWNER INSTRUCTIONS, DO NOT DESTROY
Recognize this symbol as an indication of important Safety Information!
NOTE: FLUE GAS TEMPERATURES MUST NOT EXCEED
650
o
F AT VENT SYSTEM INLET.
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND
OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY
BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW
THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUST-
MENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRI-
CAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, OR PERSONAL
INJURY OR PROPERTY DAMAGE.
!
DO NOT DESTROY. PLEASE READ CAREFULLY AND
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
MODEL SS1
INSTALLATION INSTRUCTIONS
REV. 7/02
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com
INCLUDES NEW UC1
UNIVERSAL CONTROL
Seitenansicht 0
1 2 3 4 5 6 ... 26 27

Inhaltsverzeichnis

Seite 1 - INSTALLATION INSTRUCTIONS

Copyright © 2002, Tjernlund Products, Inc. All rights reserved P/N 8504102OWNER INSTRUCTIONS, DO NOT DESTROYRecognize this symbol as an indication of

Seite 2

NOTCH BRACINGIt is recommended and local codes may dictate that the joist be reinforced as outlined below. Bracing of the rim joist is not necessary.

Seite 3 - SIDE VIEW

10INSTALLATION OF VENT PIPE If installing the SideShot Vent System on an oil or gas appliance which is not equipped with a draft hood or draft diverte

Seite 4

114. Using a tube cutter, cut the sensing tube 2" from the elbow directed at the vent pipe inlet collar, (See Diagram L). Discard the cut off se

Seite 5

ELECTRICAL WIRING All wiring from the SS1 to the appliance must be appropriate Class 1 wiring as follows: installed in rigid metal conduit, intermedia

Seite 6

13SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED TO A HONEYWELL R8184 SERIES OR EQUIVALENT PRIMARY CONTROL50/60 HzRWHITEORANGEBLACKHONEYWELLR8

Seite 7

14SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH AN AQUASTATXNRUNIVERSAL CONTROLLERLINE VOLTAGE OIL BURNERPRIMARY CONTROL, BURNERL1NXLJ1J

Seite 8

15SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH A HONEYWELL R8184 SERIES OR EQUIVALENT PRIMARY CONTROL AND A BURNER MOTOR POST-PURGE RED

Seite 9

16SIDESHOT WITH INTEGRAL UC1 CONTROL CONNECTED WITH A 24 VAC ELECTRONIC IGNITION MODULEXNRUNIVERSAL CONTROLLERD/N 9183046-8115 VAC24 VACLEGEND:HONEYWE

Seite 10

DRAFT ADJUSTMENT PROCEDUREDRAFT ADJUSTMENT PROCEDURE FOR OIL EQUIPMENTThe SideShot Vent system will properly vent a wide range of BTU/hr. input capaci

Seite 11

reading of -.02 to -.03” W.C.. IMPORTANT:If a minimum of -.02” W.C. cannot be obtained by adjusting the barometric damper closed (more draft), the

Seite 12

1Tjernlund Products welcomes your comments and questions. Address all correspondence to:Customer Service • Tjernlund Products, Inc. • 1601 Ninth Stre

Seite 13 - TJERNLUND

C. If the heater has a two stage or modulating gas valve verify that burner operates properly at both low and high fire.If the draft appears excessive

Seite 14 - UNIVERSAL CONTROLLER

Combustion Air:Modern construction methods and materials have reduced natural air infiltration rates to extremely low levels.Even older homes can lack

Seite 15

Yes, LED #1 (Amber) is lit: Verify Prover safety circuit fault does not exist. See LED indicator light status & faults, on page 20. If faults exi

Seite 16 - THERMOSTAT

REMOVAL AND REPLACEMENT OF MOTOR/WHEEL ASSEMBLY (DIAGRAM N) Disconnect power supply from the SS1 and heating equipment when making wiring connections

Seite 17 - D/N 9183046-1

23LIMITED PARTS WARRANTY AND CLAIM PROCEDURETjernlund Products, Inc. warrants the components of the SideShot for two years from date of installation.

Seite 19

BACKSIDE OF TEMPLATE B

Seite 21

2SPECIFICATIONSMotor: 115/1/60, 3300 RPM, 212 watts, 2.28 FLAFan Proving Switch: Non-adjustable, N/O with a set point of -.04" W.C.High Limit:

Seite 22

CAUTIONSThe SS1 must be installed by a qualified installer (an individual properly licensed and/or trained) in accordance with all local codes or, in

Seite 23

SS1 WITH INTEGRAL UC1 UNIVERSAL CONTROL BOARD FEATURES# 1. Power supplied by board. Do not supply power to this area or control damage may result.# 2

Seite 24

PRE / POST PURGE AND PROVER STATUS CHECK DIP SWITCH SETTINGSRemove power to SS1 and heating equipment when installing, servicing or changing dip switc

Seite 25

PLENUM AND VENT HOOD CLEARANCE FROM COMBUSTIBLESWith an inlet flue gas temperature of 650oF or below, the SideShot has been Listed for the following c

Seite 26 - BACKSIDE OF TEMPLATE B

INSTALLATIONTools required:• Reciprocating Saw • 1/2", 7/16",5/8" Wrench• Drill and 1/8", 1/4", 1/2" Bits • 1/4" Ma

Seite 27

9. Connect the Plenum to the Vent Hood of the SideShot following the steps on pages 8, 9 and 10. 10. After the SideShot is completely installed, apply