Copyright © 2002, Tjernlund Products, Inc. All rights reserved P/N 8504102OWNER INSTRUCTIONS, DO NOT DESTROYRecognize this symbol as an indication of
NOTCH BRACINGIt is recommended and local codes may dictate that the joist be reinforced as outlined below. Bracing of the rim joist is not necessary.
10INSTALLATION OF VENT PIPE If installing the SideShot Vent System on an oil or gas appliance which is not equipped with a draft hood or draft diverte
114. Using a tube cutter, cut the sensing tube 2" from the elbow directed at the vent pipe inlet collar, (See Diagram L). Discard the cut off se
ELECTRICAL WIRING All wiring from the SS1 to the appliance must be appropriate Class 1 wiring as follows: installed in rigid metal conduit, intermedia
13SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED TO A HONEYWELL R8184 SERIES OR EQUIVALENT PRIMARY CONTROL50/60 HzRWHITEORANGEBLACKHONEYWELLR8
14SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH AN AQUASTATXNRUNIVERSAL CONTROLLERLINE VOLTAGE OIL BURNERPRIMARY CONTROL, BURNERL1NXLJ1J
15SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH A HONEYWELL R8184 SERIES OR EQUIVALENT PRIMARY CONTROL AND A BURNER MOTOR POST-PURGE RED
16SIDESHOT WITH INTEGRAL UC1 CONTROL CONNECTED WITH A 24 VAC ELECTRONIC IGNITION MODULEXNRUNIVERSAL CONTROLLERD/N 9183046-8115 VAC24 VACLEGEND:HONEYWE
DRAFT ADJUSTMENT PROCEDUREDRAFT ADJUSTMENT PROCEDURE FOR OIL EQUIPMENTThe SideShot Vent system will properly vent a wide range of BTU/hr. input capaci
reading of -.02 to -.03” W.C.. IMPORTANT:If a minimum of -.02” W.C. cannot be obtained by adjusting the barometric damper closed (more draft), the
1Tjernlund Products welcomes your comments and questions. Address all correspondence to:Customer Service • Tjernlund Products, Inc. • 1601 Ninth Stre
C. If the heater has a two stage or modulating gas valve verify that burner operates properly at both low and high fire.If the draft appears excessive
Combustion Air:Modern construction methods and materials have reduced natural air infiltration rates to extremely low levels.Even older homes can lack
Yes, LED #1 (Amber) is lit: Verify Prover safety circuit fault does not exist. See LED indicator light status & faults, on page 20. If faults exi
REMOVAL AND REPLACEMENT OF MOTOR/WHEEL ASSEMBLY (DIAGRAM N) Disconnect power supply from the SS1 and heating equipment when making wiring connections
23LIMITED PARTS WARRANTY AND CLAIM PROCEDURETjernlund Products, Inc. warrants the components of the SideShot for two years from date of installation.
24
BACKSIDE OF TEMPLATE B
25
2SPECIFICATIONSMotor: 115/1/60, 3300 RPM, 212 watts, 2.28 FLAFan Proving Switch: Non-adjustable, N/O with a set point of -.04" W.C.High Limit:
CAUTIONSThe SS1 must be installed by a qualified installer (an individual properly licensed and/or trained) in accordance with all local codes or, in
SS1 WITH INTEGRAL UC1 UNIVERSAL CONTROL BOARD FEATURES# 1. Power supplied by board. Do not supply power to this area or control damage may result.# 2
PRE / POST PURGE AND PROVER STATUS CHECK DIP SWITCH SETTINGSRemove power to SS1 and heating equipment when installing, servicing or changing dip switc
PLENUM AND VENT HOOD CLEARANCE FROM COMBUSTIBLESWith an inlet flue gas temperature of 650oF or below, the SideShot has been Listed for the following c
INSTALLATIONTools required:• Reciprocating Saw • 1/2", 7/16",5/8" Wrench• Drill and 1/8", 1/4", 1/2" Bits • 1/4" Ma
9. Connect the Plenum to the Vent Hood of the SideShot following the steps on pages 8, 9 and 10. 10. After the SideShot is completely installed, apply